Go to main contents pageSpecial conditions for this system

Electrical Conditions


important

ALL racked INTEL systems (one or more), such as :

- CRM 4100,

- CRM 2400,

and

- CRM 4500,

have a current outlet type power supply (P17 type) whose male/female unit is delivered with the rack(s). The customer should supply the 3x4 mm², braid-protected, power supply cables. In the female socket, the protective braid should be connected to the "earth" terminal using the green/yellow wire.

This type of computer should be powered in accordance with the voltage and frequency characteristics indicated in the following tables.

 
VOLTAGE Single-phased 230 Volts
Tolerances between 207 V and 244 V 

Three-phased 400 Volts
Tolerances between 358 V and 423 V

FREQUENCY 50 Hz ± 1 % 
As all the electronic hardware is equipped with switch-mode power supply technology, account should be taken of the values represented below. These figures should be communicated to the supplier if it is decided to install a power supply interface (DC-AC inverter, isolating transformer, etc.).
 
POWER FACTOR 0.85
GLOBAL HARMONIC RATE < 5 %
AVERAGE FORM FACTOR 1.2
Important : Powering these devices with a neutral power system IT, referred to as "impedent neutral " is not recommended , this may lead to dysfunction.

Complementary supply :

- Provision should be made for a direct telephone line, for remote maintenance, with access to the national network, in the vicinity of the rack system .