RAISED FLOOR



For all models of NovaScale systems (one or more) and their peripherals placed in the rack or installed outside the rack, the installation of a raised floor in which the power supply and data transmission cables should be laid is necessary.

Furthermore, a raised floor serves as ventilation duct. This system is designed to deliver cooled air to the appropriate equipment and ensure good air conditioning circulation in the room

Floor resistance

The required resistance should be :


> 450 daN/m².

Floor heigth

As the plenum space is only used for laying cables and the air conditioning air discharge duct, the minimum finished height required should be :


30 cm


nota :

If this height is less than the minimum required, the plenum space should be used for laying cables only and should be totally ineffective for air conditioning blowing.