aGo to main contents pageaSpecial conditions for this système


Electrical conditions



Important

For all models of NovaScale systems (one or more) and their peripherals placed in the rack or installed outside the rack, have a current outlet type power supply (P17, brand type LEGRAND) whose male/female unit is delivered with the rack(s).

The customer should supply the 3x4 mm² (minimum), flexible, power supply cables.
If the customer provides braid-protected cable, then in the socket the protective braid should be connected to the "earth" terminal using the green/yellow wire.

This type of computer should be powered with the voltage and frequency range shown in the following table.


VOLTAGE
Single-phased 230 Volts
Tolerances between 207 V and 244 V 

FREQUENCY 50 Hz ± 1 %


As all the electronic hardware is equipped with switch-mode power supply technology, account should be taken of the values represented below. These figures should be communicated to the supplier if it is decided to install a power supply interface (U.P.S. on-line, isolating transformer, etc.).


POWER FACTOR 0,90
GLOBAL HARMONIC RATE
< 5 %
AVERAGE FORM FACTOR
1,2


Pre-requesites :

Provision should be made for a direct telephone line, for remote maintenance, with access to     the national network, in the vicinity of the rack system.


aGo to main contents pageaSpecial conditions for this système