Go to main contents page Special conditions for this system
The elements which make up a DPS 90/9x (including the console) absorb the air they need for cooling from beneath.
Air flows absorbed by the elements of the DPS 90/9x
CPU 8010 m3 /H MMU/SCU 2700 m3 /H IOP 3800 m3 /H (2100 + 1700) SYSTEM CONSOLE 1200 m3 /H
These values are given on a unitary basis.
The internal fans of a DPS 90/9x circulate the air among the elements and then expel it into the environment.
Pre-Requisites:
Openings should therefore be made in a number of the slabs of the raised floor. These should be placed under the central components so as to allow the necessary cooling air through.