Electrical Conditions


This type of computer should be powered in accordance with the voltage and frequency characteristics indicated in the following tables.

  PERIPHERALS COMPONENTS OF DPS 90/9x
VOLTAGE Single-phased 230 Volts
Tolerances between 207 V and 244 V

Three-phased 400 Volts
Tolerances between 358 V and 423 V
Single-phased 120 Volts (between Ph and N)
Tolerances between 98 V and 132V

Three-phased 208 Volts (between Phases)
Tolerances between 180 V and 229 V
FREQUENCY 50 Hz ± 1 % 60 Hz ± 1%

As all the electronic hardware is equipped with switch-mode power supply technology, account should be taken of the values represented below. These figures should be communicated to the supplier if it is decided to install a power supply interface (DC-AC inverter, isolating transformer, etc.).

POWER FACTOR 0.75
GLOBAL HARMONIC RATE < 5 %
AVERAGE FORM FACTOR 1.8