The elements which go to make up a DPS 9000/9xx (including the console) absorb the air they need for cooling from beneath.
Air flows absorbed by the elements of the DPS 9000/9xx
CSM (= EPU + SCU/MMU) 1240 m3 /h IOP 1590 m3 /h URP 1250 m3 /h CLU 70 m3 /h
These values are given on a unitary basis.
The internal fans circulate the air among the elements of a DPS 9000/9xx and then expel it into the environment.
Pre-Requisites:
Openings should therefore be made in a number of the slabs of the raised floor. These should be placed under the central components so as to allow the necessary cooling air through.