aGo to main contents page    condspec.gif (1204 bytes)Special conditions for this system


Required Air Flow


The elements which go to make up a DPS 9000/9xx (including the console) absorb the air they need for cooling from beneath.

Air flows absorbed by the elements of the DPS 9000/9xx

CSM (= EPU + SCU/MMU) 1240 m3 /h
IOP 1590 m3 /h
URP 1250 m3 /h
CLU 70 m3 /h

These values are given on a unitary basis.

The internal fans circulate the air among the elements of a DPS 9000/9xx and then expel it into the environment.

Pre-Requisites:

Openings should therefore be made in a number of the slabs of the raised floor. These should be placed under the central components so as to allow the necessary cooling air through.


aGo to main contents page    condspec.gif (1204 bytes)Special conditions for this system