Electrical Conditions


This type of computer should be powered in accordance with the voltage and frequency characteristics indicated in the following tables.

VOLTAGE Single-phased 230 Volts
Tolerances between 207 V and 244 V

Three-phased 400 Volts
Tolerances between 358 V and 423 V
FREQUENCY  50 Hz ± 1 %

As all the electronic hardware is equipped with switch-mode power supply technology, account should be taken of the values represented below. These figures should be communicated to the supplier if it is decided to install a power supply interface (DC-AC inverter, isolating transformer, etc.).

POWER FACTOR 0.65
GLOBAL HARMONIC RATE  < 5 %
AVERAGE FORM FACTOR 2

Pre-Requisites:

Provision should be made for a direct telephone line, for remote maintenance, with access to the national network, in the vicinity of the DPS 7000.

Note: On the DPS 7000s of the /5x0, /7x0, /8xxX, /Mx0 and /MTx2 series, the remote maintenance modem is housed in the table of the system console and powered by the latter's socket unit.

Presence of Mains (MVC)